Cable size and main fuses
Overview of fuse types
Electrical approval Fuse type
IEC aR
CSA/UL class RK5
1
1
Class RK5 according UL248-9
Electrical approval
SSCCR
1
IEC gG/gL type 2
2
CSA HRC form II
1
SSCCR = Standard Short Circuit Current Rating
2
gG/gL type 2 according to IEC609471-4-1, IEC60269, DIN43620, VDE0636
3
Class RK5 according UL248-9
Maximum fuse size
The pre-described fuses mentioned in the Technical Data Sheet (TDS) or on the service
diagram are the maximum main fuses to protect the installed compressor electrical panel.
The pre-described fuse types are to be used.
Final cable and fuse selection will depend on the customer’s installation and local legislation.
Installing smaller fuses of the same type/class might lead to smaller main feeder cables.
Always double-check the fuse size versus the calculated cable size. If required, reduce the
fuse size or enlarge the cable size.
Cable length should not exceed the maximum length according to IEC 60204 (table 10).
Obey local regulations if they are stricter than the examples mentioned in this document.
Package current
The Package current mentioned on the technical data sheet is defined as follows:
Package current is the current the compressor uses:
At reference conditions
At 100 % load
At maximum pressure
At nominal voltage
Before service interval (so including fouled filters, etc…)
The pre-described fuses on the technical data sheet are the maximum main fuses to protect the
installed compressor electrical panel.
Instruction book
64 9829 3178 63