Cable size
Type V Hz Approval I
nom
P
(1)
I
nom
F
F (1)
Recommended
wire section (2)
Recommended
wire section (3)
Main fuses
(A) (4)
GA 75 VSD 200 50 IEC 297 320
7 x 95 mm
2
7 x 185 mm
2
(200)
GA 75 VSD 230 50 IEC 258 281
7 x 70 mm
2
7 x 120 mm
2
(160)
GA 75 VSD 400 50 IEC 143 156
4 x 95 mm
2
or 7 x
35 mm
2
7 x 70 mm
2
200 (100)
GA 75 VSD 500 50 IEC 119 132
4 x 70 mm
2
4 x 120 mm
2
or 7
x 50 mm
2
160 (80)
GA 75 VSD 200 60 IEC 298 321
7 x 95 mm
2
7 x 185 mm
2
(200)
GA 75 VSD 230 60 IEC 258 281
7 x 70 mm
2
7 x 120 mm
2
( 160)
GA 75 VSD 380 60 IEC 150 163
4 x 95 mm
2
or 7 x
35 mm
2
7 x 70 mm
2
200 (100)
GA 75 VSD 460 60 IEC 125 137
4 x 70 mm
2
4 x 120 mm
2
or 7
x 50 mm
2
160 (80)
GA 75 VSD 200 60 CSA/UL 298 321 4 x AWG600 or 8
x AWG3/0
4 x AWG700 or 8
x AWG250
600 (300)
GA 75 VSD 230 60 CSA/UL 258 281 4 x AWG500 or 8
x AWG2/0
4 x AWG600 or 8
x AWG3/0
500 (225)
GA 75 VSD 460 60 CSA/UL 125 137 4 x AWG2/0 or 8 x
AWG3
4 x AWG3/0 or 8 x
AWG3
225 (110)
GA 75 VSD 575 60 CSA/UL 104 117 4 x AWG0 4 x AWG2/0 or 8 x
AWG3
175 (90)
Type V Hz Approval I
nom
P
(1)
I
nom
F
F (1)
Recommended
wire section (2)
Recommended
wire section (3)
Main fuses
(A) (4)
GA 90 VSD 400 50 IEC 186 200
4 x 120 mm
2
or 7
x 50 mm
2
7 x 95 mm
2
250 (125)
GA 90 VSD 500 50 IEC 155 168
4 x 95 mm
2
or 7 x
35 mm
2
7 x 70 mm
2
200 (100)
GA 90 VSD 380 60 IEC 196 209
4 x 120 mm
2
or 7
x 50 mm
2
7 x 95 mm
2
250 (125)
GA 90 VSD 460 60 IEC 162 175
4 x 95 mm
2
or 7 x
35 mm
2
7 x 70 mm
2
200 (100)
GA 90 VSD 460 60 CSA/UL 162 175 4 x AWG4/0 or 8 x
AWG2
4 x AWG250 or 8
x AWG1
300 (150)
GA 90 VSD 575 60 CSA/UL 135 148 4 x AWG3/0 or 8 x
AWG3
4 x AWG4/0 or 8 x
AWG2
250 (125)
Remarks :
(1): current in the supply lines at maximum load
(2): recommended wire section under standard conditions
(3): recommended wire section under worst case conditions
(4): recommended fuse value (value between () valid in case of 6 fuses for parallel supply cables)