For water-cooled units:
The water inlet temperature of the energy recovery system.
The water outlet temperature of the energy recovery system.
The cooling water outlet temperature of the compressor.
Modifying settings
If the programmed warning settings for the water temperatures are exceeded, a warning indication is shown
on the compressor control module:
Temperature input Unit Minimum setting Nominal setting Maximum
setting
Water inlet of energy recovery ˚C 0 50 99
Water inlet of energy recovery ˚F 32 122 210
Delay at warning signal sec 0 Consult Atlas
Copco
255
Delay at start
(Should be less than delay at warning signal)
sec 0 Consult Atlas
Copco
255
Energy recovery water outlet ˚C 0 Depends on
application
99
Energy recovery water outlet ˚F 32 Depends on
application
210
Delay at signal sec 0 Consult Atlas
Copco
255
Delay at start sec 0 Consult Atlas
Copco
255
To modify a setting, consult section Modifying parameters
Recoverable energy
The recoverable energy can be calculated by using the following formula:
RECOVERED ENERGY (kW) = 4.2 x water flow (l/s) x water temperature rise (˚C)
In the tables below, typical examples are given, except for the recovered energy.
Consult Atlas Copco for specifications.
Data for low temperature rise/high water flow (at maximum speed)
Parameter Unit GA75 VSD GA90 VSD
Recoverable energy kW 56.3 67.5
Recoverable energy hp 75.5 90.5
Water flow l/min 53.6 64.3
Water flow cfm 1.89 2.27
Temperature at inlet ˚C 55 55
Temperature at inlet ˚F 131 131
Temperature at outlet ˚C 70 70
Temperature at outlet ˚F 158 158