DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
The position setpoint is within max. error variable (outer
dead band). Is only signalled if Profinet consumer (con-
troller) has set the Fieldbus SETPOINT bit (process
representation output).
1Setpoint reached
Setpoint pos.reached
2
No signal0
Collective signal 04:
Contains the result of a disjunction (OR-operation) of all
bits comprised in bytes 13 and 14 (Not ready REMOTE
1 and Not ready REMOTE 2).
The actuator cannot be operated from REMOTE.
The actuator can only be operated via the local controls.
1Not ready REMOTE
Not ready REMOTE
3
In bytes 13 and 14, no signals are active (all bits are set
to 0).
0
An operation command in direction OPEN is performed
via the communication interface: Fieldbus OPEN or
Fieldbus SETPOINT (process representation output).
This bit remains also set during operation pauses (e.g.
due to the dead time or the reversing prevention time).
1Running OPEN
Running OPEN
4
No operation in direction OPEN is performed via the
communication interface.
0
An operation command in direction CLOSE is performed
via the communication interface: Fieldbus CLOSE or
Fieldbus SETPOINT (process representation output).
This bit remains also set during operation pauses (e.g.
due to the dead time or the reversing prevention time).
1Running CLOSE
Running CLOSE
5
No operation in direction CLOSE is performed via the
communication interface.
0
Collective signal 02:
Contains the result of a disjunction (OR-operation) of all
bits of bytes 17 to 20 (Warning 1 to Warning 4).
1Warnings
Warning
6
In bytes 17 and 20, no warnings are active (all bits are
set to 0).
0
Collective signal 03:
Contains the result of a disjunction (OR-operation) of all
bits of bytes 15 and 16 (Fault 1 and Fault 2).
The actuator cannot be operated.
1Fault
Fault
7
In bytes 15 and 16, no faults are active (all bits are set
to 0).
0
Byte 2: Actuator signals
Table 6: Byte 2: Actuator signals
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
Motor protection tripped.1Thermal fault
Thermal fault
0
No signal0
When connecting to a 3-phase AC system and with
internal 24 V DC supply of the electronics: Phase 2
is missing.
When connecting to a 3-phase or 1-phase AC system
and with external 24 V DC supply of the electronics:
One of the phases L1, L2 or L3 is missing.
1Phase failure
Phase fault
1
All phases are available.0
Selector switch is in position REMOTE.1Selector switch REMOTE
Selector sw. REMOTE
2
Selector switch is not in position REMOTE.0
Selector switch is in position LOCAL.1Selector switch LOCAL
Selector sw. LOCAL
3
Selector switch is not in position LOCAL.0
18
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profinet