DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
Limit switch in end position OPEN active.1Limit switch OPEN
Limit switch OPEN
4
No signal0
Limit switch in end position CLOSED active.1Limit switch CLOSE
Limit switch CLOSED
5
No signal0
Torque switch operated in direction OPEN1Torque switch OPEN
Torque sw. OPEN
6
No signal0
Torque switch operated in direction CLOSE1Torque switch CLOSE
Torque sw. CLOSED
7
No signal0
Bytes 3 and 4: Actual position
Byte 3 = high byte, byte 4 = low byte.
If a position transmitter (potentiometer, RWG, EWG, or MWG) is installed in the
actuator, bytes 3 and 4 are used to transmit the current actuator position.The value
is transmitted in per mil (value: 0 1,000).
Byte 5: Device status
Table 7: Byte 5: Device status
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
Collective signal 04:
Contains the result of a disjunction (OR-operation) of all
bits comprised in bytes 13 and 14 (Not ready REMOTE
1 and Not ready REMOTE 2).
The actuator cannot be operated from REMOTE.
The actuator can only be operated via the local controls.
1Not ready REMOTE
Not ready REMOTE
0
In bytes 13 and 14, no signals are active (all bits are set
to 0).
0
Collective signal 02:
Contains the result of a disjunction (OR-operation) of all
bits of bytes 17 to 20 (Warning 1 to Warning 4).
1Warnings
Warning
1
In bytes 17 and 20, no warnings are active (all bits are
set to 0).
0
Collective signal 03:
Contains the result of a disjunction (OR-operation) of all
bits of bytes 15 and 16 (Fault 1 and Fault 2).
The actuator cannot be operated.
1Fault
Fault
2
In bytes 15 and 16, no faults are active (all bits are set to
0).
0
Collective signal 09:
Indication according to NAMUR recommendation NE 107
Recommendation to perform maintenance.
Contains the result of a disjunction (OR-operation) of all
bits of byte 24 (Maintenance required).
1Maintenance required
NAMUR mainten. req.
3
In all bits of byte 24, no signals are active (all bits are set
to 0).
0
Collective signal 07:
Indication according to NAMUR recommendation NE 107
Actuator is operated outside the normal operation condi-
tions.
Contains the result of a disjunction (OR-operation) of all
bits of bytes 25 to 28 (Out of specification 1 to 4).
1Out of specification
NAMUR out of spec.
4
In bytes 25 and 28, no signals are active (all bits are set
to 0).
0
19
Actuator controls
AC 01.2/ACExC 01.2 Profinet Description of the data interface