DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
Collective signal 08:
Indication according to NAMUR recommendation NE 107
The actuator is being worked on; output signals are tem-
porarily invalid.
Contains the result of a disjunction (OR-operation) of all
bits of bytes 29 and 30 (Function check 1 and 2).
1Function check
NAMUR funct. check
5
In bytes 29 and 30, no signals are active (all bits are set
to 0).
0
Collective signal 10:
Indication according to NAMUR recommendation NE 107
Actuator function failure, output signals are invalid.
Contains the result of a disjunction (OR-operation) of all
bits of byte 23 (Failure).
1Failure
NAMUR failure
6
In all bits of byte 23, no signals are active (all bits are set
to 0).
0
Collective signal 05:
The device is ready for remote control.
No AUMA warnings, AUMA faults or signals according to
NAMUR are present.
Bit 7 is set if bits 0 to 6 are deleted.
1Device ok
Device ok
7
Contains the result of a disjunction (OR-operation) of bits
0 to 6 (device status).
0
Byte 6: Operation status
This byte stores information about actuator movement.
Table 8: Byte 6: Operation status
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
The actuator is in off-time (e.g. reversing prevention time).1Operation pause active
Operation pause active
0
No signal0
The actuator is in an intermediate position e.g. neither in
end position OPEN nor in end position CLOSED.
1In intermediate position
In intermediate pos.
1
No signal0
The actuator is within the set stepping range.1Start stepping mode
Start stepping mode
2
The actuator is outside the set stepping range.0
MPV position reached—
MPV/LPV pos. reached
3
Actuator is running (output drive is moving)
Hard wired collective signal consisting of signals:
●
(26) Running LOCAL
●
(27) Running REMOTE
●
(28) Handwheel oper.
1Actuator running
Actuator running
4
No signal0
Output drive rotates without electric operation command.1Handwheel operation
Handwheel oper.
5
No signal0
Output drive rotates due to operation command from
REMOTE.
1Running REMOTE
Running REMOTE
6
No signal0
Output drive rotates due to operation command from
LOCAL.
1Running LOCAL
Running LOCAL
7
No signal0
20
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profinet