Byte 7: Intermediate positions
Table 9: Byte 7: Intermediate positions
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
Intermediate position 1 reached1Intermediate position 1
Intermediate pos. 1
0
No signal0
Intermediate position 2 reached1Intermediate position 2
Intermediate pos. 2
1
No signal0
Intermediate position 3 reached1Intermediate position 3
Intermediate pos. 3
2
No signal0
Intermediate position 4 reached1Intermediate position 4
Intermediate pos. 4
3
No signal0
Intermediate position 5 reached1Intermediate position 5
Intermediate pos. 5
4
No signal0
Intermediate position 6 reached1Intermediate position 6
Intermediate pos. 6
5
No signal0
Intermediate position 7 reached1Intermediate position 7
Intermediate pos. 7
6
No signal0
Intermediate position 8 reached1Intermediate position 8
Intermediate pos. 8
7
No signal0
Byte 8: Discrete inputs
Table 10: Byte 8: Discrete inputs
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
A high signal (+24 V DC) is present at digital input 1.1Input DIN 1
Input DIN 1
0
No signal0
A high signal (+24 V DC) is present at digital input 2.1Input DIN 2
Input DIN 2
1
No signal0
A high signal (+24 V DC) is present at digital input 3.1Input DIN 3
Input DIN 3
2
No signal0
A high signal (+24 V DC) is present at digital input 4.1Input DIN 4
Input DIN 4
3
No signal0
A high signal (+24 V DC) is present at digital input 5.1Input DIN 5
Input DIN 5
4
No signal0
A high signal (+24 V DC) is present at digital input 6.1Input DIN 6
Input DIN 6
5
No signal0
No signal (reserved)6
No signal (reserved)7
Bytes 9 and 10: Input AIN 1
Byte 9 = high byte, byte 10 = low byte.
Byte 9 and 10 transmit the value of the first additional free analogue current input of
the Profinet interface.The start and end values can be set at the AC via push buttons
and display. (For operation, please refer to the respective operation instructions for
the actuator.)
If the measuring values are 0.3 mA below the initial value, a signal loss is indicated.
The value is transmitted in per mil (value: 0 1,000).
Bytes 11 and 12:Torque
Byte 11 = high byte, byte 12 = low byte.
21
Actuator controls
AC 01.2/ACExC 01.2 Profinet Description of the data interface