ExplanationSetting valueDefaultAccessParametersTypeID
Preserving the operation mode
REMOTE in selector switch po-
sition LOCAL or OFF depending
on the enable signal
0: Selector switch Local
0R/W
Priority REMOTE
enum3693PRM
1: Sel. sw. Local + Off
Automatic generation of enable
signal for priority REMOTE
function in case loss of fieldbus
communication
0: Off
1R/W
Fieldbus auto enable
enum3694PRM
1: On
Table 51: Customer settings > I/O interface
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 4 bytes
Setting the operation behaviour
(push-to-run operation or self-
retaining) for binary operation
commands (OPEN, STOP,
CLOSE) from remote.
0: Off (push-to-run op.)
3R/W
Self-retaining Remote
enum519PRM
1: OPEN
2: CLOSE
3: OPEN and CLOSE
4: OPEN & CL w/o STOP
Setting the self-retaining Re-
mote II mode
0: Off (push-to-run op.)
0R/W
Self-retaining Remote
II
enum533PRM
1: OPEN
2: CLOSE
3: OPEN and CLOSE
4: OPEN & CL w/o STOP
Table 52: Customer settings > Positioner
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 30 bytes
Setting the adaptive behaviour
of the positioner
0: Off
0R/W
Adaptive behaviour
enum84PRM
1: Adaptive I
Setting the outer dead band (ir-
relevant for adaptive behaviour)
Min = 1 [0.1 %]10R/W
Outer dead band
U1687PRM
Max = 100 [0.1 %]
Setting the dead time
Min = 2 [0.1 s]5R/W
Dead time
U1686PRM
Max = 600 [0.1 s]
Setting dead band OPEN (irrel-
evant for adaptive behaviour)
Min = 0 [0.1 %]5R/W
Dead band OPEN
U162012PRM
Max = 100 [0.1 %]
Setting dead band CLOSE (irrel-
evant for adaptive behaviour)
Min = 0 [0.1 %]5R/W
Dead band CLOSE
U16213PRM
Max = 100 [0.1 %]
Hysteresis in direction OPEN
(for adaptive positioner only)
Min = 0 [0.1 %]5R/W
Posit. hyst. OPEN
U162916PRM
Max = 50 [0.1 %]
Hysteresis in direction CLOSE
(for adaptive positioner only)
Min = 0 [0.1 %]5R/W
Posit. hyst. CLOSE
U162917PRM
Max = 50 [0.1 %]
Minimum dead band Xt (adapt-
ive positioner 2)
Min = 2 [0.1 %]2R/W
Dead band min. (ad.2)
U165316PRM
Max = 50 [0.1 %]
Maximum dead band Xt (adapt-
ive positioner 2)
Min = 2 [0.1 %]25R/W
Dead band max. (ad.2)
U165317PRM
Max = 50 [0.1 %]
Tolerance for the function
"Closing fully" for end position
CLOSED
Min = 0 [0.1 %]0R/W
Tolerance CLOSE
I32215PRM
Max = 50 [0.1 %]
Tolerance for the function
"Opening fully" for end position
OPEN
Min = 950 [0.1 %]1000R/W
Tolerance OPEN
I32214PRM
Max = 1000 [0.1 %]
Function Limit setting range0: Function not active
0R/W
Limit setting range
enum4167PRM
1: Function active
49