ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Failure position for OPEN-
CLOSE duty
Min = 0 [0.1 %]500R/W
Fail.pos.OPEN CLOSE
U161872PRM
Max = 1000 [0.1 %]
Failure position of multiport
valve
Min = 0 [0.1 %]500R/W
Failure position MPV
U164809PRM
Max = 1000 [0.1 %]
Table 55: Customer settings > EMCY behaviour
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 26 bytes
EMERGENCY failure reaction.
The EMERGENCY failure reac-
tion defines the actuator beha-
viour once the EMERGENCY
signal is initiated.
1: Good signal first
1R/W
EMCY fail.reac.
enum68PRM
2: Immediately active
Determines the availability of
EMERGENCY behaviour de-
pending on the selector switch
position Local or Remote
0: Remote only
0R/W
EMCY operation mode
enum67PRM
1: Remote and local
Source for EMERGENCY beha-
viour
1: I/O interface
3R/W
EMCY source
enum2924PRM
2: Fieldbus interface
3: I/O or fieldbus
4: Active interface
Actuator reaction in EMER-
GENCY operation mode
0: STOP
0R/W
EMCY operation
enum230PRM
1: CLOSE
2: OPEN
3: Approach EMCY pos.
EMERGENCY position of multi-
port valve
Min = 0 [0.1 s]10R/W
EMCY position MPV
U164808PRM
Max = 1800 [0.1 s]
Setting the EMERGENCY posi-
tion
Min = 0 [0.1 %]0R/W
EMCY position
U16231PRM
Max = 1000 [0.1 %]
By-passing the torque monitor-
ing in EMERGENCY operation
mode
0: Off
0R/W
By-pass torque
enum70PRM
1: On
By-passing the thermal monitor-
ing in EMERGENCY operation
mode
0: Off
0R/W
Thermal by-pass
enum69PRM
1: On
By-passing the timer function in
EMERGENCY operation mode
0: Off
0R/W
By-pass timer
enum71PRM
1: On
By-pass of operation profile in
EMERGENCY operation mode
0: Off
0R/W
By-pass operat.profile
enum2950PRM
1: On
By-pass of interlock function in
operation mode EMERGENCY
0: Off
0R/W
By-pass Interlock
enum3255PRM
1: On
51
Actuator controls
AC 01.2/ACExC 01.2 Profinet Appendix