ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
By-pass of local STOP function
in EMERGENCY operation
mode
0: Off
0R/W
By-pass Local STOP
enum3295PRM
1: On
Delay time for EMERGENCY
behaviour (EMERGENCY beha-
viour is only executed after the
delay time has expired).
Min = 0 [0.1 s]10R
Delay time
MMSS014015PRM
Max = 1800 [0.1 s]
Table 56: Customer settings > Timer
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 20 bytes
Setting the operation mode:
Stepping mode in direction
CLOSE
0: Off
0R/W
Step mode CLOSE
enum590PRM
1: Remote
2: Local
3: Remote and local
Setting the on time in direction
CLOSE
Min = 10 [0.1 s]50R/W
On time CLOSE
MMSS01592PRM
Max = 1800 [0.1 s]
Setting the off time in direction
CLOSE
Min = 10 [0.1 s]50R/W
Off time CLOSE
MMSS01591PRM
Max = 1800 [0.1 s]
Setting the start of stepping
mode in direction CLOSE
Min = 1 [0.1 %]1000R/W
Start stepping CLOSE
U16594PRM
Max = 1000 [0.1 %]
Setting the end of stepping
mode in direction CLOSE
Min = 0 [0.1 %]0R/W
End stepping CLOSE
U16593PRM
Max = 999 [0.1 %]
Setting the operation mode:
Stepping mode in direction
OPEN
0: Off
0R/W
Step mode OPEN
enum13PRM
1: Remote
2: Local
3: Remote and local
Setting the on time in direction
OPEN
Min = 10 [0.1 s]50R/W
On time OPEN
MMSS017PRM
Max = 1000 [0.1 s]
Setting the off time in direction
OPEN
Min = 10 [0.1 s]50R/W
Off time OPEN
MMSS018PRM
Max = 1000 [0.1 s]
52
Actuator controls
Appendix AC 01.2/ACExC 01.2 Profinet