ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Setting the start of stepping
mode in direction OPEN
Min = 0 [0.1 %]0R/W
Start stepping OPEN
U165PRM
Max = 999 [0.1 %]
Setting the end of stepping
mode in direction OPEN
Min = 1 [0.1 %]1000R/W
End stepping OPEN
U166PRM
Max = 1000 [0.1 %]
Table 57: Customer settings > Duty type monitoring
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 6 bytes
Activate/deactivate duty type
monitoring
0: Function not active
0R/W
Duty type monitoring
enum2121PRM
1: Function active
Excess of the permissible run
time within the last hour is mon-
itored. A warning is issued when
exceeding the permissible run-
ning time/h.
Min = 10 [min]15R/W
Perm. run time
U162122PRM
Max = 60 [min]
Excess of the permissible starts
within the last hour is monitored.
A warning is issued when ex-
ceeding the permissible starts.
Min = 11200R/W
Permissible starts
U162123PRM
Max = 1800
Table 58: Customer settings > Motion detector
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 12 bytes
With active motion detection the
verification is made whether the
actuator position changes due
to the manual operation within
the detection time dt by the
travel difference dx. Con-
sequently, a mechanical move-
ment can be detected at output
drive (signal: 'Handwheel opera-
tion')
0: Function not active
1R/W
Motion detector
enum2554PRM
1: Function active
Setting the detection time dt
Min = 10 [0.1 s]50R/W
Detect. time dt
MMSS012555PRM
Max = 1800 [0.1 s]
53
Actuator controls
AC 01.2/ACExC 01.2 Profinet Appendix