ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Setting the travel difference dt
Min = 10 [0.1 %]10R/W
Travel diff. dx
U162556PRM
Max = 100 [0.1 %]
The delay time defines the time
interval after terminating manual
operation until reset of the signal
'Handwheel operation'.
Min = 1 [0.001 s]6000R/W
Delay time
U163629PRM
Max = 65535 [0.001 s]
Table 59: Customer settings > Oper. time monitoring
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 4 bytes
Operation mode of operating
time monitoring. The actuator
operating time can be made in
'Manual' operation mode.
0: Off
0R/W
Operation mode
enum2546PRM
1: Manual
Perm.op. time, manual
Min = 0 [0.1 s]9000R/W
Perm.op. time, manual
MMSS012547PRM
Max = 36000 [0.1 s]
Table 60: Customer settings > Reaction monitoring
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 4 bytes
Type of actuator behaviour in
case no reaction is detected at
output drive during reaction
time. A warning (no cut-off) or a
fault (cut-off) is issued.
0: No cut-off
0R/W
Actuator behaviour
enum3157PRM
1: Cut-off
Reaction time
Min = 50 [0.1 s]150R/W
Reaction time
U163158PRM
Max = 3000 [0.1 s]
Table 61: Customer settings > Interlock
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 8 bytes
Operation mode of interlock
function
1: Remote
3R/W
Oper. mode Interlock
enum3218PRM
2: Local
3: Remote and Local
Running direction in which the
interlock function is active
1: OPEN
3R/W
Running dir. Interlock
enum3219PRM
2: CLOSE
3: OPEN and CLOSE
54
Actuator controls
Appendix AC 01.2/ACExC 01.2 Profinet