ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Source of interlock function1 : Interface
3R/W
Interlock source
enum4407PRM
2 : Fieldbus
3 : Active comm. source
Table 62: Customer settings > PVST
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 18 bytes
Setting the operation mode
PVST: Stroke = stroke-con-
trolled PVST; based on travel
across a defined stroke (stroke
PVST) within a given time
(PVST monitoring time); can be
started in any valve position
(even outside the end position)
End position test = PVST based
on test when leaving the end
position within a defined time
(PVST travel time); Can only be
started from an end position
0: Stroke
0R/W
PVST operation mode
enum4288PRM
1: End position test
PVST (Partial Valve Stroke
Test) behaviour
0: OPEN
1R/W
PVST behaviour
enum4195PRM
1: CLOSE
PVST (Partial Valve Stroke
Test) stroke
Min = 0 [0.1 %]100R/W
PVST stroke
U164193PRM
Max = 1000 [0.1 %]
PVST (Partial Valve Stroke
Test) monitoring time
Min = 10 [0.1 s]600R/W
PVST monitoring
MMSS014194PRM
Max = 3000 [0.1 s]
PVST (Partial Valve Stroke
Test) operating time
Min = 1 [0.1 s]20R/W
PVST operating time
MMSS014287PRM
Max = 600 [0.1 s]
Waiting time during PVST prior
to returning to initial position.
Min = 1 [0.1 s]20R/W
PVST reversing time
MMSS014286PRM
Max = 600 [0.1 s]
When function is active, a mes-
sage is generated if no PVST
can be executed during remind-
er period.
0: Function not active
0R/W
PVST reminder
enum4292PRM
1: Function active
Reminder period of PVST func-
tion. Generates message if no
PVST was executed during this
reminder period.
Min = 00R/W
PVST reminder period
U164289PRM
Max = 65535
Source for PVST command0: Active interface
0R/W
PVST source
enum4944PRM
1: I/O interface
2: Fieldbus interface
Table 63: Device configuration > Local controls
ExplanationSetting valueDefaultAccessParametersTypeID
Data length = 22 bytes
Signal assignment for indication
light 1 (left) on the local controls
370R/W
Indication light 1 (left)
enum160PRM
Signal assignment for indication
light 2 on the local controls
269R/W
Indication light 2
enum557PRM
Signal assignment for indication
light 3 on the local controls
270R/W
Indication light 3
enum561PRM
Signal assignment for indication
light 4 on the local controls
268R/W
Indication light 4
enum565PRM
Signal assignment for indication
light 5 (right) on the local con-
trols
369R/W
Indicat. light 5 (right)
enum569PRM
55
Actuator controls
AC 01.2/ACExC 01.2 Profinet Appendix

Related product manuals