ExplanationSetting valueDefaultAccessParametersTypeID
Setting values for parameter no.: 28-1/-2/-3/-4/-5
372: Not used
259: End position
CLOSED
258: End position OPEN
370: End p. CLOSED,
blink
369: End p. OPEN, blink
401: Setpoint
pos.reached
265: Running CLOSE
264: Running OPEN
113: Selector sw. LOCAL
115: Selector sw. RE-
MOTE
116: Selector sw. OFF
376: Limit switch
CLOSED
375: Limit switch OPEN
460:Torque sw. CLOSED
459: Torque sw. OPEN
86: NAMUR failure
84: NAMUR funct. check
83: NAMUR out of spec.
85:NAMUR mainten. req.
79: Fault
78: Warning
80: Not ready REMOTE
554: Operation pause
active
560: Start stepping mode
603: Actuator running
539: Running LOCAL
540: Running REMOTE
541: Handwheel oper.
549: In intermediate pos.
392: Intermediate pos. 1
399: Intermediate pos. 2
398: Intermediate pos. 3
397: Intermediate pos. 4
396: Intermediate pos. 5
395: Intermediate pos. 6
394: Intermediate pos. 7
393: Intermediate pos. 8
500: Input DIN 1
501: Input DIN 2
505: Input DIN 3
504: Input DIN 4
503: Input DIN 5
502: Input DIN 6
285: EMCY stop active
269: Torque fault CLOSE
268: Torque fault OPEN
56
Actuator controls
Appendix AC 01.2/ACExC 01.2 Profinet