ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Low limit setting of potentiomet-
er signal range (monitoring the
potentiometer span)
Min = 0610R/W
Low limit Uspan
U162402PRM
Max = 1023
Hysteresis of potentiometer
Min = 02R
Hysteresis
U163053PRM
Max = 10
Table 67: Device configuration > Phase monitoring
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 4 bytes
Adapt rotary direction for coun-
terclockwise rotating field
0: Function not active
1R
Adapt rotary dir.
enum1168PRM
1: Function active
Duration until phase monitoring
tripping
Min = 20 [0.1 s]100R/W
Tripping time
U16209PRM
Max = 3000 [0.1 s]
Table 68: Device configuration > Switchgear
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 2 bytes
Setting the reversing prevention
time
Min = 1 [0.1 s]3R
Revers. prevent. time
U1611PRM
Max = 300 [0.1 s]
Table 69: Device configuration > Monitoring functions
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 22 bytes
Monitoring the heating system
in the AC
0: Function not active
0R
Monitor heat. system
enum3180PRM
1: Function active
Monitoring time of heating sys-
tem (warning "Wrn heater" is is-
sued if a fault has continuously
occurred during this period)
Min = 600 [0.1 s]3000R
Heating sys. mon. time
U323991PRM
Max = 36000 [0.1 s]
Montitoring the heater in actuat-
or
0: Function not active
0R
Heater monitor
U163172PRM
1: Function active
Monitoring external 24 V DC
(external supply)
0: Function not active
0R
Monitor 24 V DC ext.
enum2798PRM
1: Function active
Monitoring 24 V DC for custom-
er (control voltage)
0: Function not active
1R/W
Monitor 24 V DC cust.
enum2865PRM
1: Function active
Duration until phase monitoring
tripping
Min = 20 [0.1 s]100R
Tripping time
U16209PRM
Max = 3000 [0.1 s]
Monitoring 24 V AC0: Function not active
1R
Monitor 24 V AC
enum2872PRM
1: Function active
Monitoring internal 24 V DC0: Function not active
1R
Monitor 24 V DC intern
enum2878PRM
1: Function active
PTC tripping device monitoring0: Function not active
0R
PTC trip. monit.
enum3232PRM
1: Function active
59
Actuator controls
AC 01.2/ACExC 01.2 Profinet Appendix