EasyManua.ls Logo

AUMA ACE C 01.2 Profinet Series - Page 60

AUMA ACE C 01.2 Profinet Series
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
RTC battery monitoring0: Function not active
1R
RTC battery test
enum4135PRM
1: Function active
Limit value (at sensor) for trigger-
ing the acceleration alarm
Min = 500 [0.001 g]1000R
Vibration alarm level
U163517PRM
Max = 4000 [0.001 g]
Table 70: Device configuration > Service interface
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 22 bytes
Information for actuator identific-
ation within the plant (e.g. KKS
designation - Power Plant Clas-
sification system)
_DEVICE-
TAG_
R/W
Device tag
S201165PRM
Settings for service operation
mode. Allows actuator control
via remote operation of service
interface depending on opera-
tion modes LOCAL or REMOTE.
0: Control: LOCAL
0R/W
Service op. mode
enum2175PRM
1: Control: LOC+REM
Table 71: Device configuration > Service functions
ExplanationSetting valueDefaultAccessParametersTypeID
Data length = 4 bytes
Creates new factory settings by
adopting the current settings
Min = 32768-1R
Create factory settings
I163486PRM
Max = 32767
Reset current settings to factory
settings
Min = 32768-1R/W
Reset factory settings
I163487PRM
Max = 32767
Table 72: General information
ExplanationSetting valueDefaultAccessParametersTypeID
Data length = 48 bytes
Torque fault OPEN active
Min = 0R
Torque fault OPEN
BOOL268PZD
Max = 1
Torque fault CLOSE active
Min = 0R
Torque fault CLOSE
BOOL269PZD
Max = 1
Selector switch1: Local
R
Selector switch
enum112PZD
2: Off
3: Remote
Actual position
Min = 0 [0.1 %]R
Actual position
U162PZD
Max = 1000 [0.1 %]
Torque
Min = 0 [0.1 %]R
Torque
U16545PZD
Max = 1000 [0.1 %]
Operation mode0: Power Off
R
Operation mode
enum120PZD
1: EMCY stop
2: Off
3: Service
4: Local
5: Interlock
6: EMERGENCY
7: Remote
8: Remote II
9: Fieldbus
10: Disabled
60
Actuator controls
Appendix AC 01.2/ACExC 01.2 Profinet

Related product manuals