ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Inner dead b. OPEN
Min = 0 [0.1 %]R
Inner dead b. OPEN
U321032PZD
Max = 1000 [0.1 %]
Inner dead b. CLOSE
Min = 0 [0.1 %]R
Inner dead b. CLOSE
U321033PZD
Max = 1000 [0.1 %]
Table 77: Diagnostic > Operation mode
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 8 bytes
On time
Min = 0R
On time
U32488PZD
Max = 3600
Number of motor starts/h
Min = 0R
No. mot. starts/h
U32489PZD
Max = 3600
Min = 0R
Incorrect dir. rotation
BOOL5241PRM
Max = 1
Table 78: Diagnostic > Process controller
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 8 bytes
Process setpoint of PID control-
ler
0 [0,1 %]R
Process setpoint
U16963PZD
1000 [0,1 %]
Actual process value of PID
controller
0 [0,1 %]R
Actual process value
U16964PZD
1000 [0,1 %]
Op. com. PID contr.
0R
Op. com. PID contr.
U32824PZD
0
Table 79: Diagnostic > Profinet > Device identification
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 196 bytes
Manufacturer ID
R
Vendor ID
U165175PRM
Ident code
R
Ident code
U163633PRM
Manufacturer name
R
Vendor name
S405154PRM
Profinet device type
R
Profinet device type
S201749PZD
Profinet device name
R
Profinet dev. name
S401669PZD
IP address
R
IP address
OS45176PRM
Subnet mask
R
Subnet mask
OS45182PRM
Gateway
R
Gateway
OS45183PRM
MAC address of Profinet module
R
MAC address module
S205205PRM
MAC address of Profinet port 1
R
MAC address port 1
S205206PRM
MAC address of Profinet port 2
R
MAC address port 2
S205207PRM
Firmware version Profinet mod-
ule
R
FW version module
S205219PRM
63
Actuator controls
AC 01.2/ACExC 01.2 Profinet Appendix