ExplanationSetting valueDefaultAccessParametersTypeID
Min = 00R/W
No.Torque-
CurvesClose
S205238PRM
Max = 65535
Interval position-time
Min = 1 [s]10R/W
Interval position-time
U164032PRM
Max = 3600 [s]
Table 86: Asset Management > Device temperatures
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 8 bytes
Temperature of actuator con-
trols
Min = -60 [°C]R
Temp. controls
I164PZD
Max = 150 [°C]
Mean value of temperature in-
formation of logic sub-assembly
Min = -100 °C]R
Temp mean value logic
I165171PRM
Max = 150 [°C]
Temperature of the control unit
Min = -60 [°C]R
Temp. control unit
I16109PZD
Max = 150 [°C]
Mean value of temperature in-
formation of optional MWG sub-
assembly
Min = -100 [°C]R
Temp mean value
MWG
I165174PRM
Max = 150 [°C]
Table 87: Asset Management > Controls version
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 6 bytes
Version for explosion-proof ap-
plications
0: Off
0R
Ex version
enum3156PRM
1: On
Version for applications with hy-
draulic actuators
0: Schuck
0R
Hydraulic version
enum5055PRM
1: Ledeen
Version for SIL applications0: Off
0R
SIL version
enum4437PRM
1: On
Table 88: Asset Management > Hardware equipment
ExplanationSetting valueDefaultAccessParametersTypeID
Data length = 46 bytes
Target configuration of 'LC'
(Local Controls/ A9) electronics
sub-assembly
0: Not available
1R
LC (target)
enum182PRM
1: Available
'LC' (Local Controls) electronics
sub-assembly (A9)
0: Not available
0R
LC
enum602PRM
1: Available
'Logic' (target configuration)
electronics sub-assembly (A2)
0: Not available
1R
Logic (target)
enum178PRM
1: Available
'Logic' electronics sub-assembly
(A2)
0: Not available
0R
Logic
enum598PRM
1: Available
Target configuration of position
transmitter
0: None
1R
Pos. transm. (target)
enum2755PRM
1: Potentiometer
2: RWG
4: MWG
Type of position transmitter
used
0: None
0R
Position transmitter
enum853PRM
1: Potentiometer
2: RWG
4: MWG
Target configuration of 'MCM'
(Motor Control and Monitoring /
A52) electronics sub-assembly
0: Not available
1R
MCM (target)
enum2337PRM
1: Available
69
Actuator controls
AC 01.2/ACExC 01.2 Profinet Appendix

Related product manuals