ExplanationSetting valueDefaultAccessParametersTypeID
'MCM' (Motor Control and Mon-
itoring / A52) electronics sub-
assembly
0: Not available
0R
MCM
enum2309PRM
1: Available
Target configuration of 'PSO'
(Power Supply Options ( A52.1)
electronics sub-assembly
0: Not available
0R
PSO (target)
enum2339PRM
1: Available
'PSO' (Power Supply Options /
A52.1) electronics sub-assembly
0: Not available
0R
PSO
enum2325PRM
1: Available
Target configuration of 'I/O inter-
face' electronics sub-assembly
(A1.0)
0: Not available
1R
I/O interface (target)
enum45PRM
1: Available
'I/O interface' electronics sub-
assembly (A1.0)
0: Not available
0R
I/O interface
enum604PRM
1: Available
Target configuration of 'I/O inter-
face 2' electronics sub-assembly
(A1.1)
0: Not available
0R
I/O interface 2 (target)
enum2415PRM
1: Available
'I/O interface 2' electronics sub-
assembly (A1.1)
0: Not available
0R
I/O interface 2
enum2399PRM
1: Available
Target configuration of 'Fieldbus'
electronics sub-assembly (A1.8)
0: No fieldbus
0R
Fieldbus (target)
enum181PRM
1: Profibus
2: Modbus
3: Foundation Fieldbus
4: HART
5: Profinet
'Fieldbus' electronics sub-as-
sembly (A1.8)
0: No fieldbus
0R
Fieldbus
enum600PRM
1: Profibus
2: Modbus
3: Foundation Fieldbus
4: HART
5: Profinet
Target configuration of 'MWG'
(magnetic limit and torque
transmitter / B6) electronics sub-
assembly
0: Not available
0R
MWG (target)
enum1752PRM
1: Available
'MWG' (magnetic limit and
torque transmitter / B6) electron-
ics sub-assembly
0: Not available
0R
MWG
enum606PRM
1: Available
Hardware configuration, target:
Target FQM available / not
available?
0 : Not available
0R
Target_FQM_available
enum5080PRM
1 : Available
Hardware configuration, actual:
Actual FQM available / not
available?
0 : Not available
0R
Target_FQM_available
enum5081PRM
1 : Available
0 : Not available
0R
Target_MotorCtrl_avail.
enum5091PRM
1 : Available
0 : Not available
0R
Actual_MotorCtrl_avail.
enum5092PRM
1 : Available
Table 89: FQM information
ExplanationSetting valueDefaultAccessParametersTypeID
Data length = 42 bytes
Target position of FQM (fail
safe) for fail safe request.
1 : FQM deactivated
R
FQM action
enum5079PRM
2 : CLOSE
3 : OPEN
The fail safe operation of FQM
is executed.
Min = 0R
FQM active
BOOL1626PZD
Max = 1