Figure 7: Connections for safety functions via FS module
For the LSO and LSC signal, the NC contact may only be used for FQM fail safe
units of variant 2 ( page 6, Valid device types).
Switching behaviour of ESD input:
Input level = high level (standard: +24 V DC)
= No safety operation for Safe ESD function
Input signal = low level (0 V DC or input open)
= Safety operation for Safe ESD function
Permissible input voltage range:
High level: +24 V DC (15 %/+20 %)
Current consumption: approx. 1 A, max. 1,2 A
Low level: max. 5 V DC
Signal behaviour of the FS ready NO/FS failure NC outputs:
Safe ESD function is ready, no fault detected by diagnostic tests is present:
FS ready NO output (NO contact) = closed
FS failure NC output (NC contact) = open
Safe ESD function is NOT ready or a fault was detected:
FS ready NO output (NO contact) = open
FS failure NC output (NC contact) = closed
Signal behaviour of LS outputs:
End position OPEN reached (XF 19-21 and XF 38-20 terminals) or End pos-
ition CLOSED reachedsignal (XF 22-24 and XF 35-23 terminals), i.e.:
Output at XF 19-21=NO or XF 22-24=NO (NO contact) terminals = closed
Output at XF 38-20=NC or XF 35-23=NC (NC contact) terminals = open
For the LSO and LSC signal, the NC contact may only be used for FQM fail
safe units of variant 2 ( page 6, Valid device types).
Permissible load at FS ready NO and LSO/LSC outputs:
Voltage range: 5 30 V
Current range 2 100 mA
For the safe signals (FS Ready/FS Failure outputs as well as LSO and LSC),
AUMA recommends the exclusive use of nominal 24 V DC signal voltages.
Table 5: Example (refer to wiring diagram pertaining to order)
Customer connectionsSignalDesignation
Wiring diagram
XF 14Digital input for Safe ESD functionESD
XF 15Reference potential for Safe ESDCom.
XF 18NO contact for FS ready/FS fault signalsFS Ready NO
XF 17NC contact for FS ready/FS fault signalsFS Failure NC
17
with non safety-related actuators Installation, commissioning and operation