Safe end position feedback safety function
Applies also for combination with of Safe ESD in direction OPEN/CLOSE.
Only the actually used (assigned) contacts must be checked. In particular for
variant 1 ( page 6, Valid device types), use of the NC contacts is not permit-
ted; checking is therefore not required.
Table 12: Proof test checklist
Configuration
Fail safe position OPEN and CLOSED (safety position OPEN and CLOSED)
1. Actuator in mid-position or at sufficient distance from the end positions?
Yes
No
check FQM end position switch:
End position OPEN not reached signal (output signal inactive), i.e.:
LSO 38-20=NC output (NC contact) = closed
LSO 19-21=NO (NO contact) output = open
End position CLOSED not reached signal (output signal inactive), i.e.:
LSC 35-23=NC output (NC contact) = closed
LSC 22-24=NO (NO contact) output = open
No fail safe fault signal may be present (FS ready signal).
2. Operation command in direction CLOSE executed?
Check actuator reaction:
Operation was triggered?
Yes
No
3. Wait until FQM end position switch tripping.
Check actuator reaction:
Operation stopped when reaching end position switch CLOSED?
End position OPEN not reached signal (output signal inactive), i.e.:
LSO 38-20=NC output (NC contact) = closed
LSO 19-21=NO (NO contact) output = open
End position CLOSED reached signal (output signal active), i.e.:
LSC 35-23=NC output (NC contact) = open
LSC 22-24=NO (NO contact) output = closed
No fail safe fault signal may be present (FS ready signal).
4. Operation command in direction OPEN executed?
Check actuator reaction:
Operation was triggered?
Start of operating time measurement.
Yes
No
5. Wait until FQM end position switch tripping.
Check actuator reaction:
Operation stopped when reaching end position switch OPEN?
Operating time measurement complete.
End position OPEN reached signal (output signal active), i.e.:
LSO 38-20=NC output (NC contact) = open
LSO 19-21=NO (NO contact) output = closed
End position CLOSED not reached signal (output signal inactive), i.e.:
LSC 35-23=NC output (NC contact) = closed
LSC 22-24=NO (NO contact) output = open
No fail safe fault signal may be present (FS ready signal).
Yes
No
Operating time for operation from end position CLOSED in direction OPEN corresponds to the actuator configuration.
6. Operate FQM via actuator into intermediate position.
Actuator in mid-position or at sufficient distance from the end positions?
35
with non safety-related actuators Checklists