2. Refer to table and check if turns/stroke of the actuator correspond to the setting
of the reduction gearing (stages 1 9).
If the setting is not correct: continue with step 3.
If the setting is correct: continue with step 6.
Table 29:
MS5.2 control unit (1 to 500 turns per stroke)
Gear stageTurns/stroke above to
11.0 1.9
21.9 3.9
33.9 7.8
47.8 15.6
515.6 31.5
631.5 62.5
762.5 125
8125 250
9250 500
Table 30:
MS50.2 control unit (10 to 5,000 turns per stroke)
Gear stageTurns/stroke above to
110.0 19.5
219.5 39.0
339.0 78.0
478 156
5156 315
6315 625
7625 1,250
81,250 2,500
92,500 5,000
3. Loosen screw [1].
4. Set crown wheel [2] to desired stage according to table.
5. Tighten screw [1].
6. Place indicator disc on shaft.
7. Set mechanical position indicator.