Table 7: User levels and authorisations
Authorisation/passwordDesignation (user level)
Verify settings
No password required
Observer (1)
Change settings
Default factory password: 0000
Operator (2)
Reserved for future extensions
Maintenance (3)
Change device configuration
e.g. type of seating, assignment of output
contacts
Default factory password: 0000
Specialist (4)
Service staff
Change configuration settings
Service (5)
AUMA administrator
AUMA (6)
6.4.1. Password entry
1.
Select desired menu and hold down push button for approx. 3 seconds.
➥
Display indicates the set user level, e.g Observer (1)
2.
Press Up ▲to select a higher user level and press Ok to confirm.
➥
Display shows: Password 0***
3.
Use push buttons Up ▲ Down ▼ to select figures 0 to 9.
4.
Confirm first digit of password via push button Ok.
5. Repeat steps 1 and 2 for all further digits.
➥
Having confirmed the last digit with Ok, access to all parameters within one
user level is possible if the password entry is correct.
6.4.2. Password change
Only the passwords of same or lower user level may be changed.
Example:The user is signed in as Specialist (4).This authorises him or her to modify
the passwords between user levels (1) to (4).
Device configuration M0053
Service functions M0222
Change passwords M0229
Menu point Service functions M0222 is only visible if user level has been set to
Specialist (4) or higher.
Select main menu
1. Set selector switch to position 0 (OFF).
2.
Press push button C Setup and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates: ▶ Display...
27
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2 Control unit: electronic (MWG)