4–41
Analog Input Gain
Default Setting: 100.0
Range: 0.0 to 300.0%
This parameter sets the ratio of analog input vs frequency output.
• Use the equation below to calculate the Analog Input Gain. For this equation, you
will need to know the minimum and maximum set-point frequencies needed for
your application.
• P4.01 to P4.04 are used when the source of frequency command is an analog
input signal (0 to +10V, -10 to +10V, 0 to 20 mA, or 4 to 20 mA).
Analog Input Reverse Motion Enable Default Setting: 00
Range: 00 Forward Motion Only
01 Reverse Motion Enable
• P4.01 to P4.04 are used when the source of frequency command is an analog
input signal (0 to +10V, -10 to +10V, 0 to 20 mA, or 4 to 20 mA).
Loss of AI2 Signal (4-20mA) Default Setting: 00
Range: 00 - Decelerate to 0Hz
01 - Stop immediately and display “EF”.
02 - Continue operation by the last frequency command
This parameter determines the operation of the drive when the ACI frequency
command is lost.
Analog Output Signal
Default Setting: 00
Range: 00 - Frequency Hz
01 - Current A
02 - PV
This parameter configures the 0-10V AO output to indicate either output
Frequency, output Current, or the PID Process Variable.
P4.11
P4.05
P4.04
Analog Gain % =
Maximum Output Frequency
Max. Frequency Reference – Min. Frequency Reference
()
x 100
P4.03