Displaying the Status of the DURAPULSE AC Drive
Press the DISPLAY key on the keypad repeatedly to cycle through the status
messages on the AC drive. The diagram below shows the order of the status
messages as you cycle through them and shows the definition of the status
messages. The status of the AC drive can be shown in RUN or STOP mode.
Actual Operating Frequency
Displays the actual operating frequency present at the T1,
T2, and T3 terminals. Example: 60.0Hz
RPM
Displays the present estimated speed of the motor.
Example: 1750 RPM
Scaled Frequency
Displays the result of output frequency x parameter
P8.01. Example: 60Hz x 1.5 = 90.0
Amps
Displays the output current present at the T1, T2, and T3
terminals. Example: 0.9A
% Motor Load
Displays the amount of load on the AC drive.
Example: (Output Current
쐦
Drive Rated Current) x 100
Output Voltage
Displays the output voltage present at the T1, T2, and T3
terminals. Example: 465V
DC Bus Voltage
Displays the DC Bus Voltage. Example: 662 VDC
PID Setpoint
Displays the PID setpoint. Note: It is possible to change
the PID setpoint with the
쒀
and
쑽
keys when the PID
setpoint value is displayed on the keypad. The PID
function (P7.00) must be enabled, and the PID Setpoint
source (P7.02) must be set to keypad (00).
PID Feedback Signal (PV)
Displays the PID feed-back signal.
Frequency Setpoint
Displays the frequency setting of the AC drive.
Example: 60.0Hz