DURAPULSE AC Drive Specifications
230V Class
Model Name: GS3-xxx 21P0 22P0 23P0 25P0 27P5
Output
Rating
Maximum Motor Output
hp
1.0 2.0 3.0 5.0 7.5
kW
0.75 1.5 2.2 3.7 5.5
Rated Output Current (A)
5 7 11 17 25
Maximum Output Voltage
Three-phase 200 to 240V (proportional to input voltage)
Rated frequency
0.1 to 400 Hz
* Input
Rating
Rated Voltage/Frequency
Single/Three-phase; 50/60 Hz;
200/208/220/230/240 VAC
Three-phase; 50/60 Hz;
200/208/220/230/240 VAC
Rated Input Current (A)
11.9 / 5.7 15.3 / 7.6 22 / 15.5 20.6 26
Voltage/Frequency Tolerance
Voltage: ± 10% Frequency: ± 5%
Short Circuit Withstand
(SCCR) (A, rms symmetrical)
5kA @ 240 VAC
Watt Loss 100% I (W)
60 82 130 194 301
Weight (lb [kg])
4.5
[2.034]
4.5
[2.034]
9.4
[4.24]
9.4
[4.24]
13.3
[6.031]
* All 3-phase power sources must be symmetrical. Do not connect DURApulse drives to
grounded, center-tapped delta transformers (which are typically used for lighting circuits).
230V Class (continued)
Model Name: GS3-xxx 2010 2015 2020 2025 2030 2040 2050
Output
Rating
Maximum Motor Output
hp
10 15 20 25 30 40 50
kW
7.5 11 15 18.5 22 30 37
Rated Output Current (A)
33 49 65 75 90 120 145
Maximum Output Voltage
Three-phase 200 to 240V (proportional to input voltage)
Rated frequency
0.1 to 400 Hz
* Input
Rating
Rated Voltage/Frequency
Three-phase,
200/208/220/230/240 VAC; 50/60 Hz
Rated Input Current (A)
34 50 60 75 90 110 142
Voltage/Frequency Tolerance
Voltage: ± 10% Frequency: ± 5%
Short Circuit Withstand
(SCCR) (A, rms symmetrical)
5kA @ 240 VAC
Watt Loss 100% I (W)
380 660 750 920 1300 1340 1430
Weight (lb [kg])
13.3
[6.031]
14.3
[6.487]
26.5
[12]
26.5
[12]
26.5
[12]
77.2
[35]
77.2
[35]
* All 3-phase power sources must be symmetrical. Do not connect DURApulse drives to
grounded, center-tapped delta transformers (which are typically used for lighting circuits).
Please review the AutomationDirect Terms and Conditions for this product.
There is no 30-day money-back guarantee on any drive over 10 hp.
Chapter 1: Getting Started
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013

Table of Contents

Related product manuals