4–65
Present Fault Record Default Setting: 00
Second Most Recent Fault Record Default Setting: 00
Third Most Recent Fault Record Default Setting: 00
Fourth Most Recent Fault Record Default Setting: 00
Fifth Most Recent Fault Record Default Setting: 00
Sixth Most Recent Fault Record Default Setting: 00
Settings for P6.31 - P6.36:
00 No Fault occurred
01 Over-current (oc)
02 Over-voltage (ov)
03 Over-temperature (oH)
04 Overload (oL)
05 Thermal Overload (oL1)
06 Over-Torque (oL2)
07 External Fault (EF)
08 CPU failure 1 (CF1)
09 CPU failure 2 (CF2)
10 CPU failure 3 (CF3)
11 Hardware Protection Failure (HPF)
12 Over-current during accel (OCA)
13 Over-current during decel (OCd)
14 Over-current during steady state (OCn)
15 Ground fault or fuse failure (GFF)
17 Input Power 3 phase loss
19 Auto Ramp Fault
20 Parameters Locked
21 PID Feedback Loss
22 Encoder Feedback Loss
23 Output Shorted(OCC)
24 Momentary Power Loss
Hunting Gain Default Setting: 0
Range: 0 to 1000
This parameter can help control frequency oscillation of motors (if needed). If
system vibration is encountered due to drive frequency hunting, reduce the
vibration by adjusting this parameter while monitoring drive/motor operation.
• This parameter is enabled only in the “high-speed regulation” control modes;
(P2.10 = 04 or 05).
• This parameter is available only with AC drive firmware v1.05 or higher.
Refer to P9.39 to determine the drive’s firmware version.
P6.37
P6.36
P6.35
P6.34
P6.33
P6.32
P6.31
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013