Chapter 4: AC Drive Parameters
4–68
Keypad PID Setpoint
Default Setting: 0.0
Range: 0.0 to 999
This parameter is used for serial communication PID setpoints.
PID Multi-setpoint 1
Default Setting: 0.0
PID Multi-setpoint 2
Default Setting: 0.0
PID Multi-setpoint 3
Default Setting: 0.0
PID Multi-setpoint 4
Default Setting: 0.0
PID Multi-setpoint 5
Default Setting: 0.0
PID Multi-setpoint 6
Default Setting: 0.0
PID Multi-setpoint 7
Default Setting: 0.0
Range for P7.11-P7.17: 0.0 to 999 Default Setting: 0.0
The Multi-Function Input Terminals DI3 to DI11 (P3.02 to P3.10) are used to
select one of the PID Multi-Setpoints. The SPs are determined by P7.11 to P7.17.
Multi-PID SP Bits
PID SP
Selection
Bit 3 Bit 2 Bit 1
OFF OFF OFF P7.02
OFF OFF
ON
P7.11: SP 1
OFF
ON
OFF P7.12: SP 2
OFF
ON ON
P7.13: SP 3
ON
OFF OFF P7.14: SP 4
ON
OFF
ON
P7.15: SP 5
ON ON
OFF P7.16: SP 6
ON ON ON
P7.17: SP 7
1) In order to use the Multi-PID SPs, P7.11 - P7.17 must be set, and P7.00
0.
2) The settings for P7.11 through P7.17 cannot exceed the setting for P7.01.
3) When all PID Multi-Setpoint inputs are off, the AC drive reverts to the PID Setpoint
Source (P7.02).
P7.17
P7.16
P7.15
P7.14
P7.13
P7.12
P7.11
The setting for P7.10 cannot exceed the setting for P7.01.
Serial communication PID setpoint uses P7.10 memory address:
Hexadecimal - 070A, MODBUS Decimal - 41803, Octal - V3412.
P7.10
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013