4–71
PID Feedback Loss Operation Default Setting: 00
Settings:
00 Warn and AC Drive Stop
01 Warn and Continue Operation
*02 Warn and Continue at Last Frequency
*03 Warn and Continue Preset Speed set in P7.28
* - Parameter setting available only with firmware v1.04 or higher (refer to P9.39)
This parameter sets the operation of the drive when there is a loss of the PID
feedback signal.
PID Feedback Loss Preset Speed Default Setting: 0.0
Range: 0 to 400.0 Hz
This parameter sets the speed of operation of the drive when there is a loss of the
PID feedback signal, and P7.27 is set to 03.
• This parameter is available only with AC drive firmware v1.04 or higher.
Refer to P9.39 to determine the drive’s firmware version.
P7.28
P7.27
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013