Chapter 4: AC Drive Parameters
4–74
Transmission Fault Treatment Default Setting: 00
Settings:
00 Display fault and continue operating
01 Display fault and RAMP to stop
02 Display fault and COAST to stop
03 No fault displayed and continue operating
This parameter is used to detect an error and take appropriate action.
Time Out Detection Default Setting: 00
Settings:
00 Disable
01 Enable
When this parameter is set to 01, the communications Time Out Detection is
Enabled. If a delay in communications for more than the Time Out Duration
(P9.05) is detected, the action selected by the Transmission Fault Treatment (P9.03)
will be used.
Time Out Duration Default Setting: 0.5
Range: 0.1 to 60.0 seconds
Parameter Lock
Default Setting: 00
Settings:
00 All parameters can be set and read
01 All parameters are read-only
Restore to Default Default Setting: 00
Settings: 0 or 99
•• Setting 99 restores all parameters to factory defaults. ••
P9.08
P9.07
P9.05
P9.04
P9.03
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013