DURAPULSE AC Drive User Manual
A–5
Line Reactors – Legacy GS Series (do not use for new installations)
Line Reactors – GS Series
460 VOLT Class – Three Phase
Part Number Rated HP Rated Amps Impedance Inductance Watts Loss
GS-41P0-LR
1 2 3% 12.0 mH 7
GS-42P0-LR
2 4 3% 6.50 mH 13
GS-43P0-LR
3 8 3% 5.00 mH 31
GS-45P0-LR
5 8 3% 3.00 mH 25
GS-47P5-LR
7.5 12 3% 2.50 mH 26
GS-4010-LR
10 18 3% 1.50 mH 29
GS-4015-LR
15 24 3% 1.20 mH 44
GS-4020-LR
22 32 3% 0.80 mH 51
GS-4025-LR
25 38 3% 0.80 mH 51
GS-4030-LR
30 45 3% 0.70 mH 64
GS-4040-LR
40 60 3% 0.50 mH 75
GS-4050-LR
50 73 3% 0.40 mH 138
GS-4060-LR
60 91 3% 0.40 mH 138
GS-4075-LR
75 105 3% 0.30 mH 123
GS-4100-LR
100 145 3% 0.20 mH 115
Line Reactors – GS Series
230 VOLT Class – Three Phase
Part Number Rated HP Rated Amps Impedance Inductance Watts Loss
GS-21P0-LR-3PH
1 5 3% 3.00 mH 7
GS-22P0-LR-3PH
2 7 3% 1.50 mH 11
GS-23P0-LR-3PH
3 11 3% 1.30 mH 23
GS-25P0-LR
5 17 3% 0.80 mH 19
GS-27P5-LR
7.5 25 3% 0.50 mH 23
GS-2010-LR
10 33 3% 0.40 mH 36
GS-2015-LR
15 49 3% 0.30 mH 33
GS-2020-LR
20 65 3% 0.25 mH 39
GS-2025-LR
25 75 3% 0.20 mH 88
GS-2030-LR
30 90 3% 0.20 mH 88
GS-2040-LR
40 120 3% 0.10 mH 95
GS-2050-LR
50 145 3% 0.10 mH 95
Appendix A: Accessories
1st Ed. Rev. D 05/2013