3–11
Motor Base Frequency Setting: 60
Range: 50/60/400 Default Setting 60
This parameter setting is determined by the motor nameplate.
Motor Base RPM Setting: 3525
Range: 375 to 24,000 RPM Default Setting: 1750
This parameter setting is determined by the motor nameplate.
Motor Maximum RPM Setting: 3600
Range: P0.03 to 24,000 RPM Default Setting: P0.03
This parameter setting is determined by the needs of the application.
Stop Methods Setting: 01
Range: 00 Ramp to Stop Default Setting: 00
01 Coast to stop
The application requires that this parameter be set to Coast to Stop.
Acceleration Time Setting: 20.0
Range: 0.1 to 600 sec Default Setting: 10 sec
The motor should accelerate from 0 RPM to Maximum Motor RPM
(P0.04) in 20 seconds.
P1.01
WARNING: If the Stop Method for the DURAPULSE AC drive is set for Coast to Stop,
the AC drive will ignore the Deceleration Time (P1.02) setting.
P1.00
WARNING: The Motor Maximum RPM parameter (P0.04) should never exceed the
maximum rpm rating for the motor you are using. If this information is not readily
available, consult your motor manufacturer.
P0.04
P0.03
P0.02