6 Parameter Settings and Functions
© Copyright Reserved Autonics Co., Ltd. 49
6 Parameter Settings and
Functions
6.1 Input
6.1.1 Input Types and Temperature Ranges
Input Types Display
Temperature
Range ()
Temperature
Range ()
Thermoco
uple
(TC)
K (CA)
1
KCaH
-200 to 1350 -328 to 2463
0.1
KCaL
-199.9 to
999.9
-199.9 to 999.9
J (IC)
1
JIcH
-200 to 800 -328 to 1472
0.1
JIcL
-199.9 to 800.0 -199.9 to 999.9
E (CR)
1
ECrH
-200 to 800 -328 to 1472
0.1
ECrL
-199.9 to 800.0 -199.9 to 999.9
T (CC)
1
TCcH
-200 to 400 -328 to 752
0.1
TCcL
-199.9 to 400.0 -199.9 to 752.0
B (PR) 1
B PR
0 to 1800 32 to 3272
R (PR) 1
R PR
0 to 1750 32 to 3182
S (PR) 1
S PR
0 to 1750 32 to 3182
N (NN) 1
N NN
-200 to 1300 -328 to 2372
C (TT)
1
1
C TT
0 to 2300 32 to 4172
G (TT)
2
1
G TT
0 to 2300 32 to 4172
L (IC)
1
LIcH
-200 to 900 -328 to 1652
0.1
LIcL
-199.9 to 900.0 -199.9 to 999.9
U (CC)
1
UCcH
-200 to 400 -328 to 752
0.1
UCcL
-199.9 to 400.0 -199.9 to 752,0
Platinel II 1
PLII
0 to 1390 32 to 2534
RTD
CU 50 0.1
CU 5
-199.9 to 200.0 -199.9 to 392.0
CU 100 0.1
CU10
-199.9 to 200.0 -199.9 to 392.0