2 Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd. 27
No(Address)
Parameter
Description
Setting range
Unit
Factory
default
TM2
TM4
4
00216(00D7)
4
00116(0073)
CH1
Ramp_Up
Rate
Ramp
up change
r
ate
0
(OFF) to 9999
//
Digit
0
4
00217(00D8)
4
00117(0074)
CH1 Ramp_Down
Rate
Ramp
down
c
hange rate
0
(OFF) to 9999
//
Digit
0
4
00218(00D9)
4
00118(0075)
CH1 Ramp Time
Unit
Ramp
time unit
0: SEC 1: MIN
2: HOUR
-
1
40
0219(00DA)
to
4
00300(012B)
40
0119
to
4
00150(0095)
CH1
reserved
4
01201(04B0)
to
4
01300(0513)
4
01101(044C)
to
4
01150(047D)
CH2
parameter - the same as above CH1
-
4
02101(0834)
to
4
02150(0865)
CH3
parameter - the same as above CH1
-
4
03101(0C 1C)
to
4
03150(0C4D)
CH4
parameter - the same as above CH1