2 Modbus Mapping Table
26 © Copyright Reserved Autonics Co., Ltd.
2.5.3 Control operation group(Func: 03/06/16, RW: R/W)
No(Address)
Parameter
Description
Setting range
Unit
Factory
default
TM2
TM4
40
0201(00C8)
4
00101(0064)
CH1 Auto
-Tuning
Execute
Auto
-tuning
e
xecute/stop
0: OFF
1: ON
-
0
4
00202(00C9)
4
00102(0065)
CH1
Heating_
Proportional Band
Heating
p
roportional band
0.1
to 999.9
10
.0
4
00203(00CA)
4
00103(0066)
CH1 Cooling_
Proportional Band
Cooling
p
roportional band
4
00204(00CB)
4
00104(0067)
CH1 Heating_
Integral Time
Heating
integral
t
ime
0
to 9999
Sec.
0
4
00205(00CC)
4
00105(0068)
CH1 Cooling_
Integral Time
Cooling
integral
t
ime
4
00206(00CD)
4
00106(0069)
CH1 Heating_
Derivation
Time
Heating
d
erivation
t
ime
0
to 9999
Sec.
0
4
00207(00CE)
4
00107(006A)
CH1 Cooling_
Derivation Time
Cooling
d
erivation
t
ime
4
00208(00CF)
4
00108(006B)
CH1 Dead_
Overlap band
In
heating &
c
ooling control
m
ode,
dead
band
PID
-PID,
PID
-
ON/OFF,
ON/OFF
-
PID
-
P BAND to
+P BAND
Digit
0.0
ON/OFF
-
ON/OFF
-
999 to 0 to
999 (H)
-999.9 to 0 to
999.9(L)
0
4
00209(00D0)
4
00109(006C)
CH1 Manual Reset
In
proportional
c
ontrol mode,
m
anual reset
0.0
to 100.0
%
50.0
4
00210(00D1)
40
0110(006D)
CH1 Heating_
ON Hysteresis
Heating
h
ysteresis
1
to 100(H)
0.1
to 100.0(L)
Digit
2
40
0211(00D2)
4
00111(006E)
CH1 Heating_
OFF Offset
Heating OFF
offset
0
to 100(H)
0.0
to 100.0(L)
Digit
0
4
00212(00D3)
40
0112(006F)
CH1 Cooling_
ON Hysteresis
Cooling
h
ysteresis
1
to 100(H)
0.1
to 100.0(L)
Digit
2
40
0213(00D4)
40
0113(0070)
CH1 Cooling_OFF
Offset
Cooling OFF
h
ysteresis
0
to 100(H)
0.0
to 100.0(L)
Digit
0
40
0214(00D5)
4
00114(0071)
CH1 MV Low Limit
MV
low-limit
s
etting value
Heating,
Cooling
0.0
to
MV High
Limit
-0.1
%
0.0
H
eating &
C
ooling
-
100.0 to 0.0
-
100.0
4
00215(00D6)
4
00115(0072)
CH1 MV High Limit
MV
high-limit
s
etting value
Heating,
Cooling
MV Low
Limit + 0.1
to
100.0
%
100.0
H
eating &
C
ooling
0
.0 to 100.0
100.0

Other manuals for Autonics TM4 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autonics TM4 Series and is the answer not in the manual?

Autonics TM4 Series Specifications

General IconGeneral
BrandAutonics
ModelTM4 Series
CategoryTemperature Controller
LanguageEnglish

Related product manuals