EasyManua.ls Logo

Autonics TM4 Series - DIN Rail Mounting

Autonics TM4 Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Modbus Mapping Table
30 © Copyright Reserved Autonics Co., Ltd.
2.5.6 Communication setting group(Func: 03/06/16, RW: R/W)
No(Address)
Parameter
Description
Setting range
Unit
Factory
default
TM2
TM4
4
00601(0258)
4
00301(012C)
Ba
udrate
Communication
s
peed
0: 2400 1: 4800
2: 9600 3: 19200
4: 38400
-
2
4
00602(0259)
4
00302(012D)
Parity Bit
Communication
p
arity bit
0: NONE 1: EVEN
2: ODD
-
0
4
00603(025A)
4
00303(012E)
Stop Bit
Communication
s
top bit
0: 1
1: 2
-
1
40
0604(025B)
4
00304(012F)
Response Waiting
Time
Response
w
aiting time
5
to 99
ms
20
4
00605(025C)
4
00305(0130)
Communication
Write
Communication
w
rite
0: ENABLE
1: DISABLE
-
0
4
00606(025D)
4
00306(0131)
Parameter Initializ
e
Parameter
i
nitialization
0: NO
1: YES
-
0
4
00607(025E)
to
4
00700(02BB)
4
00307(0132)
to
4
00350(015D)
Reserved