Hold the + + keys for 5 sec in RUN mode, to enter re-set parameter menu. Select ‘YES’ and all parameters are reset as factory
default.
Parameter 2 group :
1. Press any key among
2. Press the key once after changing the setting value, to save the setting value and move to the next parameter.
Hold the key for 3 sec to save the setting value and return to RUN mode after changing the setting value.
Dotted parameters may not appear by model type or other parameter settings.
Setting range: Refer to ‘▣ Input Type And Range’.
When changing the setting value, 5V, [IN-B, H-5V/L-5V, AL1, AL2, LBaB, AHYS] parameters of parameter 2 group are reset.
When changing the setting value, 5V, [IN-B, H-5V/ L-5V, AL1, AL2, LBaB, AHYS] parameters of parameter 2 group are reset.
Setting range: -999 to 999℃/℉(-199.9 to 999.9℃/℉
Setting range: 0.1 to 120.0 sec
Setting range: Within temperature range of each sensor [H-5V≥(L 5V+1digit)]
When changing the setting value, and 5VH-5V, 5V is reset as H-5V.
When changing the setting value, [ErMV] is reset as )0, [DI-K] is reset as OFF.
Appears only in selectable current output or SSR drive output model(TX4 – 4C).
Appears only in SSR drive output model (TX4 – 4S).
Appears only when control output[OUT] is set as CURR.Setting range: 0.5 to 120.0 sec
Appears only when control method[C-MD] is PID.
Does not appear when SSR drive output is set as CYCL, or PHAS.
Press the key to switch ‘Alarm operation’ ‘Alarm option’ setting.
Set method is same as AL1 alarm operation[AL-1].
Appears only in alarm output 2 models.
Setting range: 1 to 100℃/℉(0.1 to 50.0℃/℉)
Does not appear when AL1/AL2 alarm operation[AL-1, AL-2] is set as AM)_/SBa /LBa .
Setting range: 0 to 9999 sec (automatically set during auto-tuning)
Appears only when alarm operation[AL-1, AL-2] is set as LBa .
Setting range: 0 to 999℃/℉ (0.0 to 999.9℃/℉) (automatically set during auto-tuning)
Appears only when alarm operation [AL-1, AL-2] is set as LBa and [LBaT] is not set as 0.
Setting range: Refer to ‘▣ Input Type and Range’.
Appears only in transmission output model(TX4 -A4 ).
Setting range: 1 to 127
Setting range: 24, 48, 96, 192, 384 bps Multiply 100 to read the setting value.
Setting range: 5 to 99ms
Setting range: 0.0 to 100.0%
Only )0(OFF)/10)0(ON) appear when control method [C-MD] is set as ONOF.
When control method [C-MD] is changing PID↔ONOF and the setting value is below 10)0, it is reset as )0.
Appears in RS485 communication output model(TX4 -B4 ).
AT does not appear when control method [C-MD] is set as ONOF.
Setting range :
OFF Unlock
LOC1 Parameter 2 group lock
LOC2 Parameter 1,2 group lock
LOC3 Parameter 1,2 group, SV setting lock