Avaya IP600
Rack Mount Cabinet Installation
EXIT
. Check AC power and ground (continued)
A recommended Uninterruptible Power Supply (UPS) may be used for
power holdover. The type of UPS depends on the holdover requirements.
The UPS must provide surge protection for the RMC cabinet.
Connect cabinet grounds. See Figure 7.
The approved ground wire must be green, 6 AWG (# 40) (16mm
2
), copper,
stranded wire.
Bond all approved grounds at the single-point ground to form a single grounding
electrode system.
Connect power cord(s).