AXISA1601NetworkDoorController
RequirementsforcompliancewithUL294andUL293
ThissectioncontainsinformationandinstructionsrequiredforULcompliance.Tomakesurethe
installationisULcompliant,followtheinstructionsbelowinadditiontothegeneralinformation
andinstructionsprovidedthroughoutthisdocument.Incaseswherepiecesofinformation
contradicteachother,therequirementsforULcompliancealwaysreplacegeneralinformation
andinstructions.
PerformanceLevelsforAccessControl
ThissectioncontainsperformancelevelinformationrequiredforUL294andUL293compliance.
FeatureLevel
DestructiveAttackTestI
Security
I
EnduranceIV
StandbyPower
I
•Thecontrolpanelmustbeprogrammedtoprovidealocalaudibleoutputtoannunciate
ACpowerloss,doorheldopen,anddoorforcedopenforUL293compliance.
Supportedreaders
•ForUL294,compatibilitywiththefollowingreadershasbeenveriedbyUL:
HIDiClassRK40,AXISA4010-E.ForUL293applications,readersmustbelistedtoUL
293.ULhasnotveriedanyUL293readers.
Safetyinstructions
•TheAxisproductshallbeinstalledandservicedbyafactorytrainedprofessional.
•TheAxisproductshallbeInstalledinaccordancewiththeSecuredbyDesignHOMES
directiveforUL293compliance.
•TheAxisproductshallbeinstalledwithintheprotectedpremises(securedarea).
•TheAxisproductshallbemountedindoors.Outdoorusehasnotbeenevaluatedor
approvedbyUL.
•AllinterconnectingdevicesshallbeULlistedandClass2low-voltagepowerlimited.
•AllpoweroutputsareClass2outputs.
•AllwiringmethodsshallbeperformedinaccordancewithANSI/NFPA70,localcodesand
authoritieshavingjurisdiction.
•RecommendtouseULrecognizedgroundingwire,asizeof14-16AWG,yellow/green
color.Crimpthecableonthenon-insulatedwirepressureringterminalwhichisbeing
deliveredasasparepartoftheproduct.Importanttousepropercrimpingtooland
techniquestoensurethesafetyofproductanduser.
28