Chapter 2. MOUNTING
6
The allowable range of the mounting posture is that the upper limit is 90° (conduit
tube port becomes horizontal) and the lower limit is 45°.
Vertical
plane
Upper limit 90°
Lower limit 45°
Horizontal
plane
Side
90°
45°
Handling Precautions
Mount this unit at an appropriate angle so that it monitors the burner
from the upper slanted position. If this unit is mounted so that it moni-
tors the burner from the lower slanted position or horizontal position,
dust or soot may accumulate on the monitoring window or in the moni-
toring pipe. This may block the ultraviolet rays, causing the flame not to
be detected.
Mounting of monitoring pipe n
Materials of monitoring pipe
Use a monitoring pipe with a black inside wall. If a pipe with the stainless steel or
galvanized inside wall is used, diffused reflection of the ultraviolet rays occurs in-
side the pipe, causing a malfunction.
Size of monitoring pipe
To detect the ultraviolet rays radiation of the flame at its optimal level, it is neces-
sary to widen the light receiving area of this unit. If a recommended flame voltage
of 2.0 V or more cannot be kept, make the monitoring pipe thicker to receive a suf-
ficient amount of ultraviolet rays.
Use the monitoring pipe as thick as possible and connect the pipe to this unit
with the reducing socket.
Make the length of the monitoring pipe as short as possible. However, always
keep the operating ambient temperature within 100 °C (up to 120 °C during
flame detection).

Other manuals for Azbil AUD300C1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Azbil AUD300C1000 and is the answer not in the manual?

Azbil AUD300C1000 Specifications

General IconGeneral
BrandAzbil
ModelAUD300C1000
CategorySecurity Sensors
LanguageEnglish

Related product manuals