Operation with Field Communication software (CFS100) Azbil Corporation
6-16 Model PTG60/70/71/72 - Smart Pressure Transmitter
Measurement Range Calibration according to Actual Pressure
)RUWKH37*VHULHVVPDUWSUHVVXUHWUDQVPLWWHUVWKHPHDVXUHPHQWUDQJHPXVWEH
FDOLEUDWHGDWWZRSRLQWVQDPHO\WKH/59LQSXWYDOXHDWRXWSXWDQG859
LQSXWYDOXHDWRXWSXW
This calibration is done when calibrating actual pressures using a standard
SUHVVXUHWUDQVPLWWHU)RUIXUWKHUGHWDLOVUHIHUWR&KDSWHU³5HPRWH
&RPPXQLFDWLRQ´LQ&037*
CAUTION: If this operation is performed while the pressure transmitter process
is under automatic control, outputs may uctuate, making pressure
transmitter operation dangerous. Before performing this operation,
make sure that you switch the process control loop to manual
control.
Select DEVICE SETUPo DIAG/SERVICE o Calibration o Correct Input.
7RFDOLEUDWHWKH/59YDOXHGRXEOHFOLFN&RUUHFW,QSXW/597RFDOLEUDWHWKH
859YDOXHGRXEOHFOLFN&RUUHFW,QSXW859
A warning that the loop should be switched from automatic control to manual
PRGHLVGLVSOD\HG:$51/RRSVKRXOGEHUHPRYHGIURPDXWRPDWLF
FRQWURO$IWHUVZLWFKLQJWRPDQXDOPRGHFOLFN2.
$SSO\/59SUHVVXUH´RU³$SSO\859SUHVVXUH´LVGLVSOD\HG,IWKHYDOXHRI
WKHVWDQGDUGSUHVVXUHJHQHUDWRULVHTXDOWR/59RU859FOLFN
2.
³3UHVV2.ZKHQSUHVVXUHLVVWDEOH´LVGLVSOD\HG$IWHUFRQ¿UPLQJWKDWLQSXW
SUHVVXUHKDVVWDELOL]HGFOLFN2.
7KH³1RWH/RRSPD\EHUHWXUQHGWRDXWRPDWLFFRQWURO´PHVVDJHLV
GLVSOD\HGWRQRWLI\\RXWKDW\RXFDQQRZVZLWFKEDFNWRDXWRPDWLFFRQWURO
&OLFN2.