10
Prolonged Outdoor Storage
TrilliumSeries™ Adiabatic Products are shipped wrapped. If the unit is going to remain in
outdoor storage in excess of three months prior to installation, remove the strech-wrap and
tarp and follow the storage recommendations below.
Storage Preparation
Ensure the sump is fully drained. Remove any leaves or debris that may have
accumulated in the sump and gutters.
For extended shutdown periods after start-up, coils should be charged with nitrogen
at 15 psig in the field and capped by adding a threaded connection or a welded cap.
Upon start-up, the coil connections will require cutting.
Insert desiccant bags into the EcoFlex™ Control panel to absorb moisture. Seal the
control panel for storage.
Inspect the protective finish on the unit. Clean as required.
Motor Recommendations
TrilliumSeries Adiabatic Product motors are designed for storage at ambient
temperatures of -40ºF to 176ºF (-40ºC to 80ºC). Prolonged periods of exposure above
or below these specified conditions could degrade components of the motor and cause
malfunction or premature failure.
Care must also be taken to protect the motor from flooding or from harmful chemical
vapors.
The storage area should be free from ambient vibration. Excessive vibration can cause
damage.
Keep stored motor(s) dry and protected from weather.
Rotate the fan once per month.
Preparation After Prolonged Storage
Keep in mind that start-up procedures after long periods of storage are just as important as
pre-shutdown procedures. Follow the instructions in the rest of this manual after prolonged
storage. Be especially thorough for cleaning and inspection prior to start-up. Also, check
the battery of the EcoFlex™ Control Panel.
NOTICE: BAC units are typically
installed immediately after
shipment and many operate year
round. However, if the unit is to
be stored for a prolonged period
of time either before or after
installation, certain precautions
should be observed.