42
Additional cleaning steps that can be used to dislodge clogged coils include high
pressure air, vacuum/Shop-Vac
®
, or a mild detergent such as Nu Calgon’s Cal-Green
MX coil cleaner (use per manufacturing instructions).
The sump and water collection gutters should be cleaned immediately after cleaning
the coil to avoid clogging the pump and drain valves.
Coated coils: Inspect coil coating. To touch up blemished areas, use a Red Epoxy
Repair Kit.
Return the Pre-Cooler Pads to the original locations. See Pre-Cooler Pad Maintenance
on page 36.
Water Treatment
The sump, water distribution system, and gutters are automatically drained every 24
hours, which reduces the risk of microbiological contamination. Therefore, TrilliumSeries™
Adiabatic Products may not require water treatment. Check your local codes for treatment
requirements.
The drained water may be suitable for non-potable use such as irrigation. Refer to local
codes and regulations to determine allowable uses.
In applications where hard water is supplied to the unit, a good quality water softener may
extend the lift of the Pre-Cooler Pads.
The Pre-Cooler Pads have been treated with an algaecide to minimize the potential
for algae growth. In cases where excessive fouling is observed and is suspected to be
interfering with the airflow, the Pre-Cooler Pads should be cleaned and/or changed more
frequently.
To further optimize water use and lengthen pad life, consider ordering the Water
Monitoring Package from your local BAC Representative or enabling the Water Saver Logic.
EcoFlex™ Controls Maintenance
Setting Date and Time
The date and time are preset from the factory and do not require modification during
initial start-up or operation of the unit. However, if the unit is in storage for an extended
period of time, the date and time may need to be reset and check the battery of the
controller.
NOTE: Refer to page 28 for
more information on EcoFlex™
Controls Operation and refer to
the EcoFlex™ Controls Appendix
on page 46 for details on menu
navigation.
NOTICE: For the TSDC, one of the
Pre-Cooler Pads is smaller than
the others and must be returned to
its designated location. Follow the
yellow label of the unit to identify
the location.