WWW.BALTIMOREAIRCOIL.COM
58
Emerson
Step 1. From the general tab setting, select the above options.
NOTE: If you are using a blend gas
like R-407A in this example you
may want to find a gas that follows
the correct curve for the bubble.
CPC’s conversion does not do Dew &
Bubble it just splits the difference.
So for the SAT conversion your
conversion will always be off by half
the glide. For R-407A R-404A has
about the same bubble curve.
Step 2. Here are the setpoint tab settings. The two setpoints you will need to check are in bold. The TEMP DIF
STPT will depend on your condenser’s TD design. For the TrilliumSeries™ Adiabatic Condenser, it will most
likely be 15°F – 20°F. The TR Temperature 10 should be good but may need a little adjustment.