Recommended Maintenance Intervals
[1]
Inspect and clean as necessary: Start-Up Monthly Quarterly
Semi
Annually
Annually
Inspect general condition of the unit and check unit for
unusual noises or vibrations
Inspect sump
Flush water distribution system
Clean pump strainer(s)
Inspect Pre-Cooler Pads
[1]
Check operation of make-up valve and drain valve
Clean the optional inlet strainers
Inspect the optional pressure regulating valve
Check operation of pump(s)
Inspect coil
Run Fan Reversal Start Self-Clean Cycle
Inspect unit finish
Inspect the optional conductivity sensor
Inspect the optional pump valve and the auto-discrete valve
Mechanical equipment system: Start-Up Monthly Quarterly
Semi
Annually
Annually
Check motor voltage and current
Check general condition of the fan
Fan cycling, smooth operation
DANGER: Do not perform any
service on or near the fans,
motors, and drives, without
first ensuring that the fans are
disconnected, locked out, and
tagged out.
NOTE:
1. If removal of the pre-cooler pads is needed, only remove them when dry.
2. Recommended service intervals are the minimum for typical installations.
Different environmental conditions may dictate more frequent servicing.