7
Model Number D C
TSDC-xxx-3 1’-6” 2’-0”
TSDC-xxx-6.2 2’-4” 2’-11”
TSDC-xxx-9.6 3’-0” 3’-8”
TSDC-xxx-12.4 3'-6" 4'-0"
TSDx2-xxx-12.4 2'-8" 4'-6"
TSDx2-xxx-18.6 3'-8" 5'-6"
TSDx2-xxx-24.8 4'-3" 6'-2"
TSDx2-xxx-31.0 4'-7" 6'-8"
TSDx2-xxx-37.2 5'-3" 7'-0”
TSDx2-xxx-43.4 5'-7" 7'-3"
Table 1. Minimum Wall Separation Distance
Rigging
Layout Guidelines
Rigging
Rigging
Refer to Table 2 and Figure 4 for each unit’s required minimum spreader bar length “W1”
and the recommended minimum vertical dimension “H”. Dimension“H” is the vertical
distance from the lift point to the lifting device.
Model Number
# of
Fans H W1 W2 S
TSDC-xxx-3 1 2'-0" 3'-4" 1'-8" 2’-10”
TSDC-xxx-6.2 2 3'-1" 3'-4" 1'-8" 4’-5”
TSDC-xxx-9.6 3 5'-5" 3'-4" 1'-8" 7’-3”
TSDC-xxx-12.4 4 6'-6" 3'-4" 1'-8" 9’-8”
Model Number
# of
Fans H W L
TSDx2-xxx-12.4 4 10’-11” 5’-6” - 7’-11”
TSDx2-xxx-18.6 6 10’-11” 5’-6” - 11’-10”
TSDx2-xxx-24.8 8 10’-11” 5’-6” - 15’-9”
TSDx2-xxx-31.0 10 10’-11” 5’-6” - 19’-9”
TSDx2-xxx-37.2 12 10’-11” 5’-6” - 23’-8”
TSDx2-xxx-43.4 14 10’-11” 5’-6” - 27’-7”
Table 2. Recommended Vertical Dimension