WWW.BALTIMOREAIRCOIL.COM
57
Step 11. Go back to the Main Menu and select
Refrigeration.
Step 12. Select the Rack.
Step 13. Select Condenser. Step 14. Select Settings, starter setting: Linear Factor
2.0, Sensitivity 4.0. If saturated condensing temp
swings more than plus or minus a few degrees F then
increase Sensitivity to reduce swing.
Appendix b: Danfoss
and Emerson
Danfoss