WWW.BALTIMOREAIRCOIL.COM
21
BAC Controller Side Rack Controller (or BMS) Side
Carel
Index Description
Read/
Write Variable Name
Data
Type
Modbus
RTU
Modbus
TCP/IP BACNet SNMP
29
At least one alarm is present for the Zhiel-Abegg
fan 11
R Al_Present_ZA11 D 10030 10030 BV29 1.3.6.1.4.1.9839.2.1.1.29.0
30
At least one alarm is present for the Zhiel-Abegg
fan 12
R Al_Present_ZA12 D 10031 10031 BV30 1.3.6.1.4.1.9839.2.1.1.30.0
31
At least one alarm is present for the Zhiel-Abegg
fan 13
R Al_Present_ZA13 D 10032 10032 BV31 1.3.6.1.4.1.9839.2.1.1.31.0
32
At least one alarm is present for the Zhiel-Abegg
fan 14
R Al_Present_ZA14 D 10033 10033 BV32 1.3.6.1.4.1.9839.2.1.1.32.0
33
At least one alarm is present for the Zhiel-Abegg
fan 15
R Al_Present_ZA15 D 10034 10034 BV33 1.3.6.1.4.1.9839.2.1.1.33.0
34
At least one alarm is present for the Zhiel-Abegg
fan 16
R Al_Present_ZA16 D 10035 10035 BV34 1.3.6.1.4.1.9839.2.1.1.34.0
37 Fan Ramp is Active R FanRampActive D 10038 10038 BV37 1.3.6.1.4.1.9839.2.1.1.37.0
38
At least one alarm is present for the Ebmpapst
fan 1
R Al_Present_EBM_1 D 10039 10039 BV38 1.3.6.1.4.1.9839.2.1.1.38.0
39
At least one alarm is present for the Ebmpapst
fan 2
R Al_Present_EBM_2 D 10040 10040 BV39 1.3.6.1.4.1.9839.2.1.1.39.0
40
At least one alarm is present for the Ebmpapst
fan 3
R Al_Present_EBM_3 D 10041 10041 BV40 1.3.6.1.4.1.9839.2.1.1.40.0
41
At least one alarm is present for the Ebmpapst
fan 4
R Al_Present_EBM_4 D 10042 10042 BV41 1.3.6.1.4.1.9839.2.1.1.41.0
42
At least one alarm is present for the Ebmpapst
fan 5
R Al_Present_EBM_5 D 10043 10043 BV42 1.3.6.1.4.1.9839.2.1.1.42.0
43
At least one alarm is present for the Ebmpapst
fan 6
R Al_Present_EBM_6 D 10044 10044 BV43 1.3.6.1.4.1.9839.2.1.1.43.0
44
At least one alarm is present for the Ebmpapst
fan 7
R Al_Present_EBM_7 D 10045 10045 BV44 1.3.6.1.4.1.9839.2.1.1.44.0
45
At least one alarm is present for the Ebmpapst
fan 8
R Al_Present_EBM_8 D 10046 10046 BV45 1.3.6.1.4.1.9839.2.1.1.45.0
46
At least one alarm is present for the Ebmpapst
fan 9
R Al_Present_EBM_9 D 10047 10047 BV46 1.3.6.1.4.1.9839.2.1.1.46.0
47
At least one alarm is present for the Ebmpapst
fan 10
R Al_Present_EBM_10 D 10048 10048 BV47 1.3.6.1.4.1.9839.2.1.1.47.0
48
At least one alarm is present for the Ebmpapst
fan 11
R Al_Present_EBM_11 D 10049 10049 BV48 1.3.6.1.4.1.9839.2.1.1.48.0
49
At least one alarm is present for the Ebmpapst
fan 12
R Al_Present_EBM_12 D 10050 10050 BV49 1.3.6.1.4.1.9839.2.1.1.49.0
50
At least one alarm is present for the Ebmpapst
fan 13
R Al_Present_EBM_13 D 10051 10051 BV50 1.3.6.1.4.1.9839.2.1.1.50.0
51
At least one alarm is present for the Ebmpapst
fan 14
R Al_Present_EBM_14 D 10052 10052 BV51 1.3.6.1.4.1.9839.2.1.1.51.0
52
At least one alarm is present for the Ebmpapst
fan 15
R Al_Present_EBM_15 D 10053 10053 BV52 1.3.6.1.4.1.9839.2.1.1.52.0
53
At least one alarm is present for the Ebmpapst
fan 16
R Al_Present_EBM_16 D 10054 10054 BV53 1.3.6.1.4.1.9839.2.1.1.53.0
54 Fluid temp Sensor fail R Ain_LFT_fail D 10055 10055 BV54 1.3.6.1.4.1.9839.2.1.1.54.0
55 PreCool temp Sensor fail R Ain_PCTemp_fail D 10056 10056 BV55 1.3.6.1.4.1.9839.2.1.1.55.0
61 Head pressure below Minimum setting R LowHeadPressure D 10062 10062 BV61 1.3.6.1.4.1.9839.2.1.1.61.0
62 Low Speed Mode Enable R/W LowSpeedMode D 00063 00063 BV62 1.3.6.1.4.1.9839.2.1.1.62.0
63 Low Speed Mode Control Mode (Clock/BMS) R/W LSMControlMode D 00064 00064 BV63 1.3.6.1.4.1.9839.2.1.1.63.0
64 Low Speed Active R LowSpdActv D 10065 10065 BV64 1.3.6.1.4.1.9839.2.1.1.64.0
Table 5. Points Table (Continued)