WWW.BALTIMOREAIRCOIL.COM
25
If necessary, clean the Pre-Cooler Pads.
After installation, remove any steel shavings from inside the unit. This will prevent
shavings from rusting onto the surface of the thermosetting hybrid polymer, which
may affect the coating’s integrity over extended time.
Start-Up
Verify the correct voltage to the control panel with a meter.
Before power has been provided to the unit, proceed to flip all the breakers to the ON
position inside the control panel.
Close the control panel and ensure that both locks have been fully engaged by rotating
90 degrees on each bolt.
Remove any materials from the sump.
Turn on breaker or other power supply that supplies power to the unit.
Close the pump access hatch firmly.
Flip the main disconnect switch to the ON position.
The TrilliumSeries Adiabatic Product will start momentarily.
The EcoFlex™ Controls are pre-set from the factory. No setup is required for the
standard unit. The only setup required is for the optional Water Monitoring (see below).
More information on the EcoFlex™ Controls connections can be found on page 16.
The following items can be adjusted at the time of start-up, if desired. However,
the unit ships from the factory preset with defaults.
Precool set point
Time of daily drain
If multiple units are installed at one site, some prefer to stagger the daily drain
time a few minutes apart to manage undersized drains
Duration of daily drain
Settings for Self-Clean Cycle
Date/Time
Settings for head pressure control unit (only applicable if the option is ordered)
Communication settings (only applicable if the option is ordered)
Water saving logic or energy saving logic
Auto-Discrete logic (only applicable if the option is ordered)
More information on EcoFlex™ Controls Operation can be found on page 28 and
more information on EcoFlex™ Controls Maintenance can be found on page 40.
Setting the Parameters for the Water Monitoring Option
TrilliumSeries™ Adiabatic Products can be ordered with a sensor that monitors the water
quality so that water is bled out only when needed. Without this package, the water will
be bled at preset intervals. This package also comes with a water consumption meter that
can be set to measure consumption over defined intervals of time. Please use the following
procedure to set those intervals. This option monitors the amount of purged from the
Condenser given the following conditions:
The pressure regulating valve provided by BAC is properly field installed and set to 20.
NOTE: It is imperative that both
bolts are fully engaged to maintain
the control panel’s NEMA 4 rating.
Unit Operation
Start-Up
General
Inspection
Cleaning
Start-Up
Setting the Parameters for the
Water Monitoring Option