Power Connections
The ER-500 monitor has two power supply options. The first power supply is an internal lithium 3.6V DC D size cell that powers
the monitor for about six years when no outputs are used. The monitor can also be powered by a 4…20 mA current loop.
See Figure 4. If the current loop is used, a sensing circuit within the monitor detects the presence of the current loop and
automatically disconnects the battery from the circuit.
JP1
JP2
JP3
Input Total Pulse Signal
P1
Freq. In
4-20mA
Iso Total Pluse
TR_B
TR_A
RS485 Gnd
Setpoint 1
Setpoint 2
Gnd
+
+
+
Total Reset
OC Total Pluse
Signal Gnd
TB1
Mag
Pulse
Iso
OC
Low
High
4-20 mA
Current Loop
(10 …28V DC)
Load
10
…28V DC
Figure 4: Loop power connections
Installation